How Can We Help?
Pneumatic Retrofits
Verdant Retrofit Guide
Pneumatic Retrofits
Pneumatic controls can still be found in some buildings. In this scenario, water control valves have pneumatic actuators that are controlled by a pneumatic thermostat in the room. There is a separate electric switch that controls fan speeds. For this type of retrofit there are two options:
Keep all the controls at line-voltage
Migrate all the system to 24VAC.
In most cases, option 1 is the simplest since valves and fan selector switches are usually close to each other. If this is the case, the voltage adapter (FCA-47) is required to control the fan speeds. For controlling the pneumatic water valves, a 3-way electro pneumatic (EP) valve is needed for each valve needing control. The 3-way EP valve will be installed in the pneumatic tubing feeding each water valve. The 3-way EP valve will be connected in the same way as the fail position of the water valve. For example, in colder climates, the heating valve will fail open. The 3-way EP valve can then be connected using the normally open (NO) port to the pneumatic tubing feeding the water valve. The 3-way EP valve opening signal voltage needs to match the line voltage of the fan coil.
Option 2 is a better solution when the water valves and fan speed selectors are not relatively close or where valve location is not easily accessible in the room. In this case, the 3-way EP’s are selected to use 24VAC as the driving voltage and for controlling the fan speeds, you will need to add a 24VAC relay per fan speed. A new 24VAC transformer needs to be installed as well, which could complicate the install and increase costs of the retrofit.